DOL Motor Starter Supply and Control with Thermistor Protection – Performance Level e (PL e) example

This example shows the power supply and control of a direct-on-line (DOL) motor starter, including an additional thermistor protection relay for monitoring the motor temperature.

The three-phase supply is taken from the busbar -L1, -L2 and -L3 and connected to the motor circuit breaker -Q4. The motor circuit breaker provides protection for the motor circuit against short circuits and overloads.

The protected three-phase supply is then connected to two power contactors, -Q5 and -Q6, which are connected in series. Both contactors must be energized to supply power to the motor. Using two contactors provides redundant switching for the safety-related motor shutdown function.

The contactors -Q5 and -Q6 are controlled by the safety output Q320.1. Their feedback contacts are connected to PLC input I302.3, allowing the control system to monitor the switching state of the contactors and detect a failure to open.

The motor circuit also includes a Siemens thermistor motor protection relay -KT1. The relay monitors the motor temperature through its thermistor connections T1 and T2. If the motor temperature exceeds the permitted limit, the thermistor relay changes its output contact state, providing a signal to the control system.

The thermistor relay feedback is connected to PLC input I302.1, allowing the PLC to monitor the motor thermal protection status.

The motor circuit breaker -Q4 also provides an auxiliary feedback signal to PLC input I302.2, allowing the control system to monitor the status of the motor protection device.

Safety Note

This redundant contactor arrangement is designed to achieve Performance Level e (PL e) for the motor safety function in accordance with EN ISO 13849-1, as part of the machinery safety requirements of the Machinery Directive 2006/42/EC.

The achieved Performance Level must be confirmed through the complete safety-system design, including the required calculations, component characteristics, diagnostics, and validation. The contactor wiring alone does not establish PL e independently of the complete safety function.