VFD Frequency Converter Power Supply and Connections example

This example shows the power supply and main electrical connections of an ABB ACS880 frequency converter used to control the speed and operation of an electric motor.

The three-phase supply is taken from the busbar L1, L2 and L3 and connected through the motor circuit breaker -Q13 to the frequency converter -TA1. The circuit breaker provides protection and a means of disconnecting the frequency converter from the main supply. Its auxiliary contact provides a feedback signal to the PLC input I303.5, allowing the control system to monitor the status of the motor circuit breaker.

The frequency converter is supplied with a PE connection to ensure that its protective earthing requirements are met. A separate 24 VDC supply, provided from the UPS-backed supply, is also connected to the converter for its auxiliary control power.

The drawing shows the motor power connections at terminals T1/U, T2/V and T3/W, which provide the variable-frequency output used to control the motor. The connection points for the brake resistor are also shown, allowing a braking resistor to be connected when required by the application.

The frequency converter includes an FPTC-01 thermistor protection module. This module provides two motor thermistor monitoring channels, with the corresponding signals connected to PLC inputs I2030.3 and I2050.3. This allows the control system to receive motor temperature protection signals.

The drawing also shows the Safe Torque Off (STO) connections, which form part of the drive's safety-related control interface. In addition, the communication interfaces are represented, including the FENA-21 PROFINET module and the drive-to-drive link.

The second page shows the additional connection details for the ABB ACS880 frequency converter -TA1. While the previous drawing provides an overview of the drive's power supply and main electrical interfaces, these pages focus on the individual control and signal connections available on the frequency converter.

The drawing is organized into several sections according to the type of I/O connection:

  • XDI – Digital inputs: Shows the individual digital input channels and their corresponding addresses, including I2000.0 to I2000.5.

  • XDIO – Digital inputs/outputs: Shows the configurable digital input/output connections.

  • XRO – Relay outputs: Shows the relay output terminals, including their NO, NC and common connections.

  • XAI – Analog inputs: Shows the analog input terminals, reference voltage connections and associated signal addresses.

  • XAO – Analog outputs: Shows the analog output terminals and their corresponding signal addresses.

For each connection, the table provides dedicated fields for the reference, symbolic address and function text. These fields make it possible to document how each frequency converter I/O point is used in the electrical system and identify the corresponding signal in the control system.

The third page shows the FS0-12 safety module which is used for fail safe connections and applications for the ACS880.

The drawing is organized into several sections according to the type of I/O connection:

  • X113 – Fail safe digital inputs and outputs.

  • X114 – Fail safe digital inputs and outputs.

  • X111 – (STO) Safe torque off connections.

For each connection, the table provides dedicated fields for the reference, symbolic address and function text. These fields make it possible to document how each frequency converter I/O point is used in the electrical system and identify the corresponding signal in the control system.